Amps to kW Calculator
This amps to kW calculator works out the real power a circuit or supply delivers from its current, voltage and power factor. It covers single-phase, three-phase and DC, and shows the apparent power in kVA alongside, so you can see what a fuse, breaker or supply rating means in kilowatts of usable load.
Single-phase at 230 V
This converts a current into power. It does not check whether a cable or circuit can carry that current, which needs a qualified electrician to BS 7671.
Talk to PES about your supplyHow the amps to kW calculator works
Power in watts is current multiplied by voltage, adjusted for the power factor on an AC supply. Divide by 1,000 to get kilowatts. On a three-phase supply the current flows in three conductors, so the formula includes the square root of 3 (about 1.732) when you use the line to line voltage.
Single-phase AC
Three-phase AC (line to line voltage)
Use the current per phase and the line to line voltage, 400 V on a standard UK supply.
Three-phase AC (line to neutral voltage)
If you only know the phase voltage, 230 V in the UK, use this version. For a balanced load it gives the same answer as the line to line formula.
DC
DC has no power factor. A 100 A load on a 48 V battery system is 100 × 48 ÷ 1,000 = 4.8 kW.
Worked examples
A 32 A EV charging circuit
A dedicated 32 A single-phase circuit at 230 V with a power factor of 1 delivers 32 × 230 ÷ 1,000 = 7.36 kW. That is why single-phase chargers are sold as 7.4 kW units. The same 32 A on a 400 V three-phase supply gives 1.732 × 400 × 32 ÷ 1,000 = 22.17 kW, the basis of the 22 kW three-phase charger. To see what that power costs, try the EV charging cost calculator.
A 100 A three-phase supply
A small business on a 100 A per phase, 400 V supply has 1.732 × 400 × 100 ÷ 1,000 = 69.28 kVA of capacity. With a power factor of 0.9, the most real power it can deliver is 69.28 × 0.9 = 62.35 kW. If the site is planning new machinery or chargers that would take it past that figure, it will need a larger supply and a move to CT metering.
Amps to kW conversion table
UK voltages: 230 V single-phase and 400 V three-phase line to line. Three-phase figures use the current per phase.
| Amps | 1-phase 230 V, PF 1 | 3-phase 400 V, PF 1 | 3-phase 400 V, PF 0.9 |
|---|---|---|---|
| 6 A | 1.38 kW | 4.16 kW | 3.74 kW |
| 10 A | 2.30 kW | 6.93 kW | 6.24 kW |
| 13 A | 2.99 kW | 9.01 kW | 8.11 kW |
| 16 A | 3.68 kW | 11.09 kW | 9.98 kW |
| 20 A | 4.60 kW | 13.86 kW | 12.47 kW |
| 25 A | 5.75 kW | 17.32 kW | 15.59 kW |
| 32 A | 7.36 kW | 22.17 kW | 19.95 kW |
| 40 A | 9.20 kW | 27.71 kW | 24.94 kW |
| 50 A | 11.50 kW | 34.64 kW | 31.18 kW |
| 63 A | 14.49 kW | 43.65 kW | 39.28 kW |
| 80 A | 18.40 kW | 55.43 kW | 49.88 kW |
| 100 A | 23.00 kW | 69.28 kW | 62.35 kW |
| 125 A | 28.75 kW | 86.60 kW | 77.94 kW |
| 160 A | 36.80 kW | 110.85 kW | 99.77 kW |
| 200 A | 46.00 kW | 138.56 kW | 124.71 kW |
| 250 A | 57.50 kW | 173.21 kW | 155.88 kW |
| 315 A | 72.45 kW | 218.24 kW | 196.41 kW |
| 400 A | 92.00 kW | 277.13 kW | 249.42 kW |
Why amps to kW matters for a business
Most of the ratings on a site are in amps: the main fuse, the incoming breaker, the distribution boards and the circuits that feed each machine. Your bills, your equipment and your energy contract are in kW, kVA and kWh. Converting between them tells you how much load a supply can actually carry before it trips or goes over capacity.
The power factor matters here. A site with a poor power factor draws more current for the same kW, so it reaches the limit of its supply and its agreed capacity sooner. The kW to kVA calculator shows how much capacity a low power factor uses up, and the kW to amps calculator runs the conversion the other way when you are sizing new load.
If the numbers show you are close to the limit of your supply, or you are adding load, we can review your capacity and supply contract and tender it across the market. Any changes to circuits or protection should be designed by a qualified electrician to BS 7671.
Frequently asked questions
How many kW is 32 amps?
On a 230 V single-phase supply with a power factor of 1, 32 A is 7.36 kW. On a 400 V three-phase supply it is 22.17 kW, or 19.95 kW at a power factor of 0.9.
How many kW is 100 amps three-phase?
A 100 A per phase supply at 400 V is 69.28 kVA. At a power factor of 1 that is 69.28 kW, and at a power factor of 0.9 it is 62.35 kW.
How many kW is a 13 amp plug?
A 13 A plug on a 230 V supply can deliver up to 13 × 230 = 2,990 W, or 2.99 kW. That is why the largest plug-in heaters and kettles are rated at about 3 kW.
How many kW is 16 amps?
16 A at 230 V single-phase is 3.68 kW. On a 400 V three-phase supply, 16 A per phase is 11.09 kW at a power factor of 1, which is the basis of 11 kW EV chargers.
How do you convert amps to kW?
For single-phase, multiply amps by volts and the power factor, then divide by 1,000. For three-phase, multiply by 1.732 as well, using the line to line voltage: 63 A at 400 V and a power factor of 1 is 1.732 × 400 × 63 ÷ 1,000 = 43.65 kW.
What power factor should I use?
Use 1 for resistive loads such as heaters, kettles and EV chargers. Use 0.8 to 0.95 for motor loads such as pumps, fans and compressors, and 0.9 if you are not sure for a mixed business site.
Why is kVA higher than kW?
kVA is apparent power and kW is the real power that does useful work. kW equals kVA multiplied by the power factor, so a 100 A three-phase supply of 69.28 kVA delivers only 62.35 kW at a power factor of 0.9.
Running out of supply capacity? We can check your capacity, review your supply contract and tender it across the market.
Get in touchRelated tools and services
- kW to Amps CalculatorSingle-phase, three-phase and DC, with the working
- Three Phase Power CalculatorkW, kVA and kVAr from volts, amps and power factor
- kW to kVA CalculatorApparent and reactive power from kW and power factor
- EV Charging Cost CalculatorCost per charge and per mile, fleet totals and a site check
- Compare business energyTender your contract across the market
- All free calculatorsEvery PES energy and electrical calculator