kW to kVA Calculator
This kW to kVA calculator converts real power into apparent power using the power factor, and shows the reactive power in kVAr that makes up the difference. It is the conversion you need when you size a generator or transformer, or check a site’s load against its agreed supply capacity, because all three are set in kVA rather than kW.
100 kW at a power factor of 0.9
How to convert kW to kVA
kW is real power, the part that does useful work such as heating, lighting or turning a motor. kVA is apparent power, the total the supply has to deliver, including the reactive power that motors, transformers and some lighting draw to set up their magnetic fields. The power factor is the ratio between the two.
At a power factor of 1 the two figures are the same. The lower the power factor, the more kVA you need for the same kW. You can find a site’s power factor from half-hourly data with the power factor calculator.
Worked examples
Sizing a standby generator
Generators are rated in kVA at a standard power factor of 0.8. A site that needs 80 kW of standby power needs 80 ÷ 0.8 = 100 kVA of generator. Turn it round and a 100 kVA generator delivers 80 kW of real power. Buying on kW alone and assuming the two match would leave the generator undersized by a fifth.
A factory with a poor power factor
A factory with 400 kW of peak demand and a power factor of 0.8 draws 400 ÷ 0.8 = 500 kVA, with 300 kVAr of reactive power. Correcting the power factor to 0.95 brings the same load down to 400 ÷ 0.95 = 421.1 kVA, freeing 78.9 kVA of capacity without changing a single machine.
kW to kVA conversion table
| kW | PF 0.8 | PF 0.9 | PF 0.95 |
|---|---|---|---|
| 5 kW | 6.3 kVA | 5.6 kVA | 5.3 kVA |
| 10 kW | 12.5 kVA | 11.1 kVA | 10.5 kVA |
| 15 kW | 18.8 kVA | 16.7 kVA | 15.8 kVA |
| 20 kW | 25.0 kVA | 22.2 kVA | 21.1 kVA |
| 25 kW | 31.3 kVA | 27.8 kVA | 26.3 kVA |
| 30 kW | 37.5 kVA | 33.3 kVA | 31.6 kVA |
| 40 kW | 50.0 kVA | 44.4 kVA | 42.1 kVA |
| 50 kW | 62.5 kVA | 55.6 kVA | 52.6 kVA |
| 75 kW | 93.8 kVA | 83.3 kVA | 78.9 kVA |
| 100 kW | 125.0 kVA | 111.1 kVA | 105.3 kVA |
| 150 kW | 187.5 kVA | 166.7 kVA | 157.9 kVA |
| 200 kW | 250.0 kVA | 222.2 kVA | 210.5 kVA |
| 250 kW | 312.5 kVA | 277.8 kVA | 263.2 kVA |
| 300 kW | 375.0 kVA | 333.3 kVA | 315.8 kVA |
| 400 kW | 500.0 kVA | 444.4 kVA | 421.1 kVA |
| 500 kW | 625.0 kVA | 555.6 kVA | 526.3 kVA |
| 750 kW | 937.5 kVA | 833.3 kVA | 789.5 kVA |
| 1,000 kW | 1,250.0 kVA | 1,111.1 kVA | 1,052.6 kVA |
Why kW to kVA matters for a business
Generators and transformers are rated in kVA
The heat a generator or transformer can handle depends on the current it carries, not on how much of that current does useful work. That is why both are rated in kVA. A 500 kVA transformer can supply 500 kW only at a power factor of 1. At 0.8 it is fully loaded at 400 kW.
Your agreed capacity is in kVA
A half-hourly supply has an agreed supply capacity (ASC) in kVA, and you pay a capacity charge for it every day. If your kVA demand goes over it, excess capacity charges are added to the bill. A site that runs at a power factor of 0.8 needs 25% more kVA than its kW load, so it either pays for a larger ASC or risks going over the one it has. Convert your capacity to current with the kVA to amps calculator.
A poor power factor wastes capacity you pay for
Network operators also charge half-hourly sites for excess reactive power, which typically applies when the power factor falls below about 0.95. Power factor correction equipment can cut both the reactive power charges and the capacity a site needs, and it often pays back within a few years on sites with large motor loads. If you want to check whether your capacity and charges are right, we can review your supply contract as part of a tender. To go the other way, from kVA to real power, use the kVA to kW calculator.
Frequently asked questions
How many kVA is 100 kW?
At a power factor of 0.8, 100 kW is 125 kVA. At 0.9 it is 111.1 kVA, and at 0.95 it is 105.3 kVA.
How do you convert kW to kVA?
Divide the kW by the power factor. A 50 kW load at a power factor of 0.9 is 50 ÷ 0.9 = 55.6 kVA.
What size generator do I need for 100 kW?
Generators are rated at a power factor of 0.8, so 100 kW needs a 125 kVA generator before any allowance for motor starting or future load. A 100 kVA generator delivers only 80 kW.
Is kVA always higher than kW?
kVA is equal to or higher than kW. They are the same only at a power factor of 1. At 0.9, kVA is 11.1% higher than kW, and at 0.8 it is 25% higher.
What is kVAr?
kVAr is reactive power, the part of the supply that motors and transformers use to build magnetic fields without doing useful work. A 100 kW load at a power factor of 0.9 draws 111.1 kVA and 48.4 kVAr.
How much capacity does a poor power factor waste?
A 400 kW load at a power factor of 0.8 needs 500 kVA of capacity. Corrected to 0.95, the same load needs 421.1 kVA, freeing 78.9 kVA of agreed capacity.
What power factor should I use?
Use 0.8 for generator sizing, because that is how generators are rated. Use 0.9 for a typical mixed business site and 1 for purely resistive loads such as heaters. Half-hourly data shows your site’s actual figure.
Paying for capacity you cannot use? We can review your agreed capacity and supply contract and tender it across the market.
Get in touchRelated tools and services
- Power Factor CalculatorPF, kVAr correction and reactive charge costs
- kVA to kW CalculatorReal power from any kVA rating, with kVAr
- kVA to Amps CalculatorCurrent per phase for supplies and transformers
- kW to Amps CalculatorSingle-phase, three-phase and DC, with the working
- Compare business energyTender your contract across the market
- All free calculatorsEvery PES energy and electrical calculator