kVA to kW Calculator

Use this kVA to kW calculator to find how much real power a generator, UPS, transformer or electricity supply can deliver. Enter the kVA rating and the power factor and it gives the kW, the reactive power in kVAr and the current the rating corresponds to on a UK 400 V three-phase supply.

Free calculator

Convert kVA to kW

kVA

Generators and many UPS units are rated at a power factor of 0.8, so 0.8 is filled in. For a typical business site use 0.9 to 0.95. Use 1 for purely resistive loads such as heaters.

Real power
80kW

From 100 kVA at a power factor of 0.8

Reactive power60 kVAr
Full-load current, 400 V three-phase144.3 A per phase
Metering at that currentCT metered (above 100 A)
WorkingkW = 100 kVA × 0.8 = 80 kW. kVAr = √(100² − 80²) = 60 kVAr

A generator or transformer must be sized on kVA as well as kW. Check both against the nameplate.

Talk to PES about your supply

How the kVA to kW calculator works

kVA is apparent power: the voltage multiplied by the current, with no allowance for how much of that current does useful work. kW is real power, the part that runs motors, lights and heaters. The power factor links the two. It is a number between 0 and 1, and a site full of motors and transformers has a lower power factor than one full of heaters.

kW = kVA × power factor
kVAr = √(kVA² − kW²)

kVAr is reactive power. It flows back and forth to build the magnetic fields in motors and transformers, so it loads the cables and the supply but does no work. At a power factor of 1 there is none and kVA equals kW.

Which power factor to use

Generators are rated in kVA at a power factor of 0.8. That is the industry convention: the alternator is built to deliver its full kVA at 0.8, and the engine is sized to supply the matching kW. Many UPS units are rated the same way, though newer ones are often rated at 0.9 or 1, so check the datasheet. For a typical business site, 0.9 to 0.95 is realistic. A site with power factor correction equipment may run at 0.97 or better. If you have a half-hourly meter, your data shows the kWh and kVArh, which gives your actual power factor.

Worked example: sizing a standby generator

A distribution warehouse has a peak demand of 420 kW at a power factor of 0.9, which is 420 ÷ 0.9 = 466.7 kVA. A 500 kVA generator looks big enough on kVA, but at its rated 0.8 power factor it delivers only 500 × 0.8 = 400 kW, which is 20 kW short. The next common size, 630 kVA, gives 630 × 0.8 = 504 kW and covers the load with headroom. Always check a generator against both figures.

Worked example: what a supply capacity delivers

A factory has an agreed supply capacity of 200 kVA. At a power factor of 0.95 it can draw 200 × 0.95 = 190 kW before it reaches that capacity. If its power factor drops to 0.85, the same 200 kVA delivers only 170 kW. The 20 kW difference is capacity the site pays for but cannot use for real work. Our power factor calculator shows how much correction would recover it.

Worked example: a transformer

A 1,000 kVA site transformer supplies 1,000 × 0.9 = 900 kW at a power factor of 0.9, and 1,000 × 0.8 = 800 kW at 0.8. Transformers are rated in kVA because their heating depends on current, whatever the power factor of the load.

kVA to kW conversion table

Common generator, UPS, transformer and supply sizes, with the full-load current on a 400 V three-phase supply.

kVAkW at PF 0.8kW at PF 0.9kW at PF 1.0Current at 400 V
10 kVA8.0 kW9.0 kW10.0 kW14.4 A
20 kVA16.0 kW18.0 kW20.0 kW28.9 A
30 kVA24.0 kW27.0 kW30.0 kW43.3 A
45 kVA36.0 kW40.5 kW45.0 kW65.0 A
60 kVA48.0 kW54.0 kW60.0 kW86.6 A
69 kVA55.2 kW62.1 kW69.0 kW99.6 A
100 kVA80.0 kW90.0 kW100.0 kW144.3 A
150 kVA120.0 kW135.0 kW150.0 kW216.5 A
200 kVA160.0 kW180.0 kW200.0 kW288.7 A
250 kVA200.0 kW225.0 kW250.0 kW360.8 A
315 kVA252.0 kW283.5 kW315.0 kW454.7 A
400 kVA320.0 kW360.0 kW400.0 kW577.4 A
500 kVA400.0 kW450.0 kW500.0 kW721.7 A
630 kVA504.0 kW567.0 kW630.0 kW909.3 A
800 kVA640.0 kW720.0 kW800.0 kW1,154.7 A
1,000 kVA800.0 kW900.0 kW1,000.0 kW1,443.4 A
1,250 kVA1,000.0 kW1,125.0 kW1,250.0 kW1,804.2 A
1,500 kVA1,200.0 kW1,350.0 kW1,500.0 kW2,165.1 A
2,000 kVA1,600.0 kW1,800.0 kW2,000.0 kW2,886.8 A

The current depends only on kVA and voltage, so it is the same at every power factor. To work from current instead, use the kVA to amps calculator, or go the other way with the kW to kVA calculator.

Why kVA and kW both matter for a business

A half-hourly metered site has an agreed supply capacity, set in kVA, and pays a capacity charge for every kVA of it each day whether it uses it or not. The network has to carry the full current, so it charges on kVA rather than kW. Go over that capacity and excess capacity charges apply, often at a higher rate.

That makes power factor a cost issue. A site at 0.85 needs about 12% more kVA than the same load at 0.95 to deliver the same kW. Many sites also pay reactive power charges when their power factor falls below about 0.95. Correcting power factor can lower the capacity you need to book, and with it a fixed charge that shows up on every bill.

A few points apply whenever you size or buy equipment. Whole-current meters handle up to 100 A per phase, about 69 kVA on a three-phase supply, and anything bigger needs CT metering. Generator and UPS sizing should also allow for motor starting currents and future load, which a qualified engineer should assess. If you are reviewing your capacity or your contract, PES can check both and tender your supply across the market.

Frequently asked questions

How many kW is 100 kVA?

100 kVA is 80 kW at a power factor of 0.8, the standard generator rating. It is 90 kW at a power factor of 0.9 and 100 kW at a power factor of 1.

How do you convert kVA to kW?

Multiply the kVA by the power factor. A 250 kVA supply at a power factor of 0.9 delivers 250 × 0.9 = 225 kW.

Why are generators rated at a power factor of 0.8?

It is the industry convention. The alternator is built to deliver its full kVA at a power factor of 0.8 and the engine is sized for the matching kW, so a 500 kVA generator supplies 400 kW.

Is kVA the same as kW?

Only at a power factor of 1, for purely resistive loads such as heaters. For any load with motors or transformers, kW is lower than kVA. At a power factor of 0.9, 100 kVA is 90 kW.

How many kW is a 1,000 kVA transformer?

A 1,000 kVA transformer supplies 800 kW at a power factor of 0.8, 900 kW at 0.9 and 950 kW at 0.95. Its rating is in kVA because its heating depends on current, not on the power factor of the load.

How much real power can my agreed supply capacity deliver?

Multiply the capacity in kVA by your site’s power factor. A 200 kVA capacity delivers 190 kW at a power factor of 0.95 but only 170 kW at 0.85.

What is kVAr?

kVAr is reactive power, the power that builds the magnetic fields in motors and transformers without doing useful work. It equals the square root of kVA squared minus kW squared, so 100 kVA at a power factor of 0.8 has 60 kVAr.

How many amps is 100 kVA?

100 kVA draws 144.3 A per phase on a 400 V three-phase supply and 434.8 A on a 230 V single-phase supply. The current depends on kVA and voltage, not on the power factor.

Not sure your supply capacity fits your load? We can check your capacity and power factor and tender your supply contract across the market.

Get in touch