kW and Watts to Amps Calculator
Single-phase at 230 V
This shows the load current. Cable and protective device sizing must be done by a qualified electrician to BS 7671.
Talk to PES about your supplyHow to convert kW or watts to amps
To turn kilowatts or watts into amps you need the power, supply voltage and, on an AC supply, the power factor. If your figure is in kW, multiply it by 1,000 to get watts. Then divide by voltage and power factor. On a three-phase supply you also divide by the square root of 3 (about 1.732). The unit switch means one page covers both kW-to-amps and watts-to-amps calculations without a duplicate tool.
Single-phase AC
Example: a 7 kW EV charger on a 230 V supply with a power factor of 1 draws 7,000 ÷ 230 = 30.4 A. That is why home and workplace 7 kW chargers sit on a dedicated 32 A circuit. To see what those chargers cost to run, try our EV charging cost calculator.
Three-phase AC (line to line voltage)
Example: a 50 kW compressor on a 400 V three-phase supply at a power factor of 0.85 draws 50,000 ÷ (1.732 × 400 × 0.85) = 84.9 A per phase.
Three-phase AC (line to neutral voltage)
If you only know the phase voltage, 230 V in the UK, use this version. It gives the same answer as the line to line formula for a balanced load.
DC
DC has no power factor. A 2 kW load on a 48 V battery system draws 2,000 ÷ 48 = 41.7 A.
kW to amps conversion table
UK voltages: 230 V single-phase and 400 V three-phase.
| kW | 1-phase 230 V, PF 1 | 3-phase 400 V, PF 1 | 3-phase 400 V, PF 0.9 |
|---|---|---|---|
| 1 kW | 4.3 A | 1.4 A | 1.6 A |
| 2 kW | 8.7 A | 2.9 A | 3.2 A |
| 3 kW | 13.0 A | 4.3 A | 4.8 A |
| 5 kW | 21.7 A | 7.2 A | 8.0 A |
| 7 kW | 30.4 A | 10.1 A | 11.2 A |
| 10 kW | 43.5 A | 14.4 A | 16.0 A |
| 11 kW | 47.8 A | 15.9 A | 17.6 A |
| 15 kW | 65.2 A | 21.7 A | 24.1 A |
| 20 kW | 87.0 A | 28.9 A | 32.1 A |
| 22 kW | 95.7 A | 31.8 A | 35.3 A |
| 30 kW | 130.4 A | 43.3 A | 48.1 A |
| 40 kW | 173.9 A | 57.7 A | 64.2 A |
| 50 kW | 217.4 A | 72.2 A | 80.2 A |
| 75 kW | 326.1 A | 108.3 A | 120.3 A |
| 100 kW | 434.8 A | 144.3 A | 160.4 A |
| 150 kW | 652.2 A | 216.5 A | 240.6 A |
| 200 kW | 869.6 A | 288.7 A | 320.8 A |
| 250 kW | 1,087.0 A | 360.8 A | 400.9 A |
| 500 kW | 2,173.9 A | 721.7 A | 801.9 A |
Why the answer matters for a business
The current a site draws decides how its electricity is metered and what it pays for capacity. Up to 100 A per phase, a supply can use a whole-current meter. Above that, the cables pass through current transformers (CTs) and the meter reads a scaled-down current, which is normal for most sites with more than about 69 kVA of three-phase load.
Current also tells you how close you are to your agreed supply capacity. Adding EV chargers, heat pumps or new machinery without checking can push a site over its capacity and into excess capacity charges on every bill. If you are planning new load, check the numbers first and talk to us about the supply contract and capacity that fit.
Frequently asked questions
How do you convert watts to amps?
For DC or a resistive single-phase load, divide watts by volts. At 230 V, 1,000 W draws 1,000 ÷ 230 = 4.35 A. For AC motors and other non-resistive loads, also divide by the power factor.
How many amps is 1 kW?
On a 230 V single-phase supply with a power factor of 1, 1 kW is 4.35 A. On a 400 V three-phase supply it is 1.44 A per phase, or 1.60 A at a power factor of 0.9.
How many amps is a 7 kW EV charger?
A 7 kW single-phase charger draws about 30.4 A at 230 V and runs on a dedicated 32 A circuit. Chargers sold as 7.4 kW are 32 A units, because 32 A × 230 V is 7.36 kW. It is the most common size for workplace and home charging.
How many amps is 10 kW three-phase?
At 400 V and a power factor of 1, 10 kW draws 14.4 A per phase. At a power factor of 0.9 it draws 16.0 A per phase.
How do you convert kW to amps on a three-phase supply?
Multiply the kW by 1,000, then divide by 1.732, the line to line voltage and the power factor. A 50 kW load at 400 V and a power factor of 0.85 draws 50,000 ÷ (1.732 × 400 × 0.85) = 84.9 A per phase.
What power factor should I use?
Use 1 for resistive loads such as heaters, kettles and EV chargers. Use 0.8 to 0.95 for motor loads such as pumps, fans and compressors. If you have a half-hourly meter, your bill or data may show your site’s actual power factor.
What is the difference between kW and kVA?
kW is real power, the energy that does useful work. kVA is apparent power, which includes the reactive power that motors and transformers draw. kVA equals kW divided by the power factor. Supply capacity is agreed in kVA, so a poor power factor uses up capacity you are paying for.
Can I use this to size a cable or breaker?
No. It gives the load current only. Cable size and protection depend on installation method, length, grouping and temperature, and must be designed by a qualified electrician to BS 7671.
Adding load to your site? We can check your capacity, review your supply contract and tender it across the market.
Get in touchRelated tools and services
- kVA to Amps CalculatorCurrent per phase for supplies and transformers
- Amps to kW CalculatorReal power from current, voltage and power factor
- Three Phase Power CalculatorkW, kVA and kVAr from volts, amps and power factor
- EV Charging Cost CalculatorCost per charge and per mile, fleet totals and a site check
- Compare business energyTender your contract across the market
- All free calculatorsEvery PES energy and electrical calculator