kVA to Amps Calculator

This kVA to amps calculator turns the apparent power of a supply, transformer or generator into the current it carries on each phase. UK business supplies are agreed and sized in kVA, but meters, fuses, switchgear and cables are rated in amps, so this is the conversion you need when you compare a site’s capacity with the equipment that serves it.

Free calculator

Convert kVA to amps

kVA
Supply type
V

For three-phase, enter the line to line voltage: 400 V on a standard UK low voltage supply.

Current
144.3A

Per phase, three-phase at 400 V line to line

Smallest standard rating that covers it160 A
MeteringCT metered (above 100 A)
Whole-current limit at this voltage69.3 kVA
WorkingI = 100 kVA × 1,000 ÷ (1.732 × 400 V) = 144.3 A

This shows the load current. Cable and protective device sizing must be done by a qualified electrician to BS 7671.

Talk to PES about your supply

How to use the kVA to amps calculator

kVA is apparent power, the product of voltage and current. Because it already includes the reactive power that motors and transformers draw, you do not need a power factor to convert kVA to amps. You only need the supply voltage and whether the supply is single-phase or three-phase.

Three-phase (line to line voltage)

Amps per phase = kVA × 1,000 ÷ (1.732 × volts)

On a standard UK 400 V supply, each kVA carries 1.44 A per phase. A 100 kVA supply carries 100,000 ÷ (1.732 × 400) = 144.3 A per phase.

Single-phase

Amps = kVA × 1,000 ÷ volts

On a 230 V single-phase supply, each kVA carries 4.35 A. A 15 kVA single-phase supply carries 15,000 ÷ 230 = 65.2 A.

Worked examples

A 500 kVA transformer

A 500 kVA ground-mounted transformer feeding a factory at 400 V delivers up to 500,000 ÷ (1.732 × 400) = 721.7 A per phase at full load. The main switchboard would typically have an 800 A incomer, the next standard rating up.

A retail unit with 69 kVA

A shop with an agreed capacity of 69 kVA at 400 V draws up to 69,000 ÷ (1.732 × 400) = 99.6 A per phase. That sits just inside the 100 A per phase limit for whole-current metering, which is why 69 kVA is the usual dividing line between whole-current and CT metered three-phase supplies.

kVA to amps table

Current at 400 V three-phase line to line, with 230 V single-phase shown for the smaller sizes. Above about 25 kVA, UK supplies are almost always three-phase.

kVA 3-phase 400 V Standard rating Metering 1-phase 230 V
15 kVA 21.7 A 25 A Whole current 65.2 A
25 kVA 36.1 A 40 A Whole current 108.7 A
50 kVA 72.2 A 80 A Whole current 217.4 A
69 kVA 99.6 A 100 A Whole current 300.0 A
100 kVA 144.3 A 160 A CT Not used
150 kVA 216.5 A 250 A CT Not used
200 kVA 288.7 A 315 A CT Not used
250 kVA 360.8 A 400 A CT Not used
315 kVA 454.7 A 500 A CT Not used
400 kVA 577.4 A 630 A CT Not used
500 kVA 721.7 A 800 A CT Not used
630 kVA 909.3 A 1,000 A CT Not used
800 kVA 1,154.7 A 1,250 A CT Not used
1,000 kVA 1,443.4 A 1,600 A CT Not used
1,500 kVA 2,165.1 A 2,500 A CT Not used
2,000 kVA 2,886.8 A 3,200 A CT Not used

The standard rating is the smallest common breaker or fuse size at or above the full-load current. It is a guide only: protection must be selected by a qualified electrician to BS 7671.

Why kVA to amps matters for a business

Your agreed supply capacity is set in kVA

Every half-hourly supply has an agreed supply capacity (ASC), the maximum kVA the network operator has reserved for the site. You pay a daily capacity charge for it on every bill, whether you use it or not, and if your demand goes over it you pay excess capacity charges as well. Converting the ASC to amps lets you check it against the rating of your main incomer and see how much headroom is left before adding EV chargers, heat pumps or new machinery.

Transformer sizes and the current they carry

Larger sites take their supply from a dedicated 11 kV to 400 V transformer. Pole-mounted units are often 25 to 200 kVA, and ground-mounted units are typically 315, 500, 800, 1,000 or 1,500 kVA. A 1,000 kVA transformer carries 1,443.4 A per phase at full load, so the low voltage switchgear behind it is usually rated at 1,600 A. If your ASC is well below your transformer size, you may be able to raise it without new plant. If it is close, more capacity can mean a costly connection upgrade.

The 69 kVA whole-current threshold

Whole-current meters carry the full supply current and are limited to 100 A per phase, which at 400 V is about 69 kVA. Above that, the supply needs current transformer (CT) metering, where the meter reads a scaled-down current. If you are moving past this threshold or need more capacity, we can review your capacity and supply contract as part of a tender.

If you know the load in kW rather than kVA, use the kW to amps calculator, which takes the power factor into account. To turn kVA into real power, try the kVA to kW calculator, or work through a full three-phase load with the three-phase power calculator.

Frequently asked questions

How many amps is 100 kVA?

A 100 kVA three-phase supply at 400 V carries 144.3 A per phase. That is above the 100 A whole-current limit, so a 100 kVA supply is CT metered and would typically have a 160 A incomer.

How many amps is a 500 kVA transformer?

At full load, a 500 kVA transformer with a 400 V secondary delivers 721.7 A per phase. The low voltage switchgear is usually rated at 800 A, the next standard size up.

How many amps is a 1,000 kVA transformer?

A 1,000 kVA (1 MVA) transformer at 400 V carries 1,443.4 A per phase at full load. Its main breaker is typically rated at 1,600 A.

How do you convert kVA to amps on a three-phase supply?

Multiply the kVA by 1,000, then divide by 1.732 and the line to line voltage. For 250 kVA at 400 V, that is 250,000 ÷ (1.732 × 400) = 360.8 A per phase.

How many amps is 15 kVA single-phase?

At 230 V, 15 kVA is 15,000 ÷ 230 = 65.2 A. The same 15 kVA on a 400 V three-phase supply is only 21.7 A per phase.

What is 69 kVA in amps?

69 kVA at 400 V three-phase is 99.6 A per phase. Exactly 100 A per phase is 69.3 kVA, which is the upper limit for a whole-current meter, so larger supplies need CT metering.

Do I need a power factor to convert kVA to amps?

No. kVA already includes reactive power, so current depends only on kVA and voltage. You need the power factor only when you start from kW, because kVA equals kW divided by the power factor.

Can I use this to size a cable or breaker?

No. It gives the full-load current only. Cable size and protection depend on installation method, length, grouping and temperature, and must be designed by a qualified electrician to BS 7671.