Power Factor Calculator and Correction
This power factor calculator works out your site’s power factor from kW and kVA, or from kW, volts and amps, then shows how much correction in kVAr you need to reach a target and what poor power factor is costing you in reactive power charges. It is built for UK half-hourly metered sites, where power factor shows up on the bill.
Below 0.95, so your network operator can charge for reactive power
- Real power
- 85 kW
- Apparent power
- 100 kVA
- Reactive power
- 52.7 kVAr
- Phase angle
- 31.8°
- Correction needed
- 24.7 kVAr
- Bank size, rounded up to 5 kVAr
- 25 kVAr
- kVA after correction
- 89.5 kVA
- Capacity and current freed
- 10.5 kVA (10.5%)
- Annual energy at this load
- 340,000 kWh
- Excess reactive energy a year
- 98,960 kVArh
- Reactive charges a year now
- £297
- After correction
- £0
- Capacity charge saving a year
- Saving a year
- £297
- Simple payback
Reactive charges apply to half-hourly metered sites. The estimate assumes a steady load and power factor; real sites vary, so size a bank from logged data and a survey.
Ask PES to check your reactive chargesWhat power factor is
An AC supply carries two kinds of power. Real power, in kW, does useful work: heat, light and turning shafts. Reactive power, in kVAr, is the magnetising current that motors, transformers and fluorescent ballasts need to operate. It does no work but still flows through your cables and the network. Apparent power, in kVA, is the total the supply has to carry.
A site with lots of motors, pumps and compressors typically sits at 0.75 to 0.9 lagging, which means the network carries 11 to 33% more current than the work needs.
How to use the power factor calculator
With half-hourly bill or meter data, use the kW and kVA mode with readings from the same period. With a clamp meter reading, use the volts and amps mode, which works out the kVA first:
For the kVA side of the triangle on its own, the kW to kVA calculator and the kVA to amps calculator handle the conversions.
Power factor correction: how much kVAr you need
Capacitors supply reactive power locally, so less of it has to come through the network. The correction needed to move from one power factor to another is:
Worked example: an 85 kW site at 0.85
A site drawing 85 kW and 100 kVA has a power factor of 0.85, a phase angle of 31.8° and 52.7 kVAr of reactive power. To reach 0.95 it needs 85 × (0.620 − 0.329) = 24.7 kVAr, so in practice a 25 kVAr bank. After correction it draws 85 ÷ 0.95 = 89.5 kVA, freeing 10.5 kVA of capacity and cutting the current by 10.5%.
Worked example: a three-phase workshop
A workshop on a 400 V supply draws 250 A per phase while using 140 kW. Its apparent power is 1.732 × 400 × 250 ÷ 1,000 = 173.2 kVA, so its power factor is 140 ÷ 173.2 = 0.808. Reaching 0.95 takes 56.0 kVAr, so a 60 kVAr bank. That brings the demand down to 147.4 kVA, freeing 25.8 kVA. At 4,000 hours a year and 0.3p/kVArh, its reactive charges are about £672 a year before correction.
Correction table: kVAr per kW of load
Multiply your load in kW by the figure in the table. For example, 100 kW at 0.80 needs 42.1 kVAr to reach 0.95.
| Power factor now | To 0.95 | To 0.98 | To 1.00 |
|---|---|---|---|
| 0.70 | 0.692 | 0.817 | 1.020 |
| 0.75 | 0.553 | 0.679 | 0.882 |
| 0.80 | 0.421 | 0.547 | 0.750 |
| 0.85 | 0.291 | 0.417 | 0.620 |
| 0.90 | 0.156 | 0.281 | 0.484 |
| 0.92 | 0.097 | 0.223 | 0.426 |
Why network operators charge for reactive power
Reactive current heats cables and transformers and uses up network capacity just as real current does, so the distribution network operator (DNO) charges for it. On a half-hourly supply, the excess reactive power charge applies to the kVArh in each half hour above 33% of the kWh, which is the same as a power factor of about 0.95. Your supplier passes it through as a bill line in p/kVArh. A site at 0.95 or better pays nothing on it.
Power factor also hits the capacity charge. Your agreed supply capacity is set in kVA, so a site at 0.85 needs about 12% more kVA than the same load at 0.95, and pays for it every day. If you are near your limit, correction can avoid an excess capacity charge or a costly upgrade.
Capacitor banks
Most sites correct power factor with a capacitor bank at the main switchboard; the calculator’s payback section shows whether one is worth it. A fixed bank suits a steady load. An automatic bank switches capacitor steps in and out as the load changes, so it holds the target without over-correcting into a leading power factor when the site is quiet. Sites with variable speed drives or other harmonic sources need a detuned bank, which has reactors to stop the capacitors resonating with the harmonics. Size one from a survey with a few weeks of logged data.
Why power factor matters for a business: payback
The saving from correction has up to three parts: the reactive charges that disappear, any capacity charge saved by lowering your agreed capacity and a small cut in cable and transformer losses. For the 85 kW example, the reactive charges are about £297 a year at 0.3p/kVArh. If the freed 10.5 kVA lets you lower your agreed capacity at 5p/kVA a day, that adds about £192 a year. On a quote of £1,500, the simple payback would be about 5.1 years on reactive charges alone, or 3.1 years with the capacity saving.
Correction pays back fastest on large, steady motor loads with a poor power factor. Before you buy, check what you actually pay on your bill. You can check the three-phase load itself with the three-phase power calculator. If you want a second opinion on your reactive and capacity charges, or your supply contract, talk to PES.
Frequently asked questions
How do you calculate power factor?
Divide real power in kW by apparent power in kVA. A site drawing 85 kW and 100 kVA has a power factor of 85 ÷ 100 = 0.85.
What is a good power factor?
0.95 or above. Below 0.95, network operators charge half-hourly sites for the excess reactive power, so most sites aim for 0.95 to 0.98 after correction.
How much kVAr do I need to correct power factor?
Multiply the kW by tan(acos(current PF)) minus tan(acos(target PF)). Taking an 85 kW load from 0.85 to 0.95 needs 85 × (0.620 − 0.329) = 24.7 kVAr, so a 25 kVAr capacitor bank.
What is a reactive power charge?
It is a network charge for reactive energy, measured in kVArh, above an allowance of about a third of your kWh, which is the same as a power factor of 0.95. At 0.3p/kVArh, an 85 kW site at a power factor of 0.85 running 4,000 hours a year pays about £297 a year.
What is the difference between kW, kVA and kVAr?
kW is real power that does useful work, kVAr is reactive power that motors and transformers need to run and kVA is the total the supply has to carry. They form a right-angled triangle, so kVA² = kW² + kVAr²; 85 kW and 52.7 kVAr make 100 kVA.
Is power factor correction worth it?
It depends on your charges. Correcting an 85 kW site from 0.85 to 0.95 saves about £297 a year in reactive charges at 0.3p/kVArh and frees 10.5 kVA of capacity. If that lets you lower your agreed capacity at 5p/kVA a day, it saves about £192 a year more.
Does power factor affect my electricity bill?
Yes, if you are half-hourly metered. Reactive charges appear as a separate line, and your capacity charge is set in kVA, so a site at 0.85 needs about 12% more capacity than the same load at 0.95. Smaller non half-hourly sites are not charged for reactive power.
Can you over-correct power factor?
Yes. Too much capacitance makes the power factor leading, which can raise the voltage and interact with harmonics. Automatic capacitor banks avoid this by switching steps in and out to match the load.
Paying reactive power charges or close to your capacity? We can review your half-hourly data, size the correction and tender your supply contract.
Get in touchRelated tools and services
- kW to kVA CalculatorApparent and reactive power from kW and power factor
- kVA to kW CalculatorReal power from any kVA rating, with kVAr
- Three Phase Power CalculatorkW, kVA and kVAr from volts, amps and power factor
- kVA to Amps CalculatorCurrent per phase for supplies and transformers
- Compare business energyTender your contract across the market
- Talk to PESReview your reactive and capacity charges
- All free calculatorsEvery PES energy and electrical calculator