Power Factor Calculator and Correction

This power factor calculator works out your site’s power factor from kW and kVA, or from kW, volts and amps, then shows how much correction in kVAr you need to reach a target and what poor power factor is costing you in reactive power charges. It is built for UK half-hourly metered sites, where power factor shows up on the bill.

Free calculator

Power factor and correction

What you know

Both figures are on a half-hourly bill or in your meter data. Use readings from the same half hour, or a month’s kWh and kVAh divided by the same hours.

Correction and reactive charges

Hours a year is your annual kWh divided by this kW load. 4,000 hours is a long single shift; 8,760 is round the clock. The reactive rate is on your bill as excess reactive power or kVArh; 0.3p/kVArh is a typical figure, and it varies by network area and voltage.

Work out the payback on a capacitor bank

Add the capacity charge only if you plan to lower your agreed supply capacity after correction. It is on a half-hourly bill as the availability or capacity charge.

Power factor
0.85lagging

Below 0.95, so your network operator can charge for reactive power

Real power
85 kW
Apparent power
100 kVA
Reactive power
52.7 kVAr
Phase angle
31.8°
Correction to 0.95
Correction needed
24.7 kVAr
Bank size, rounded up to 5 kVAr
25 kVAr
kVA after correction
89.5 kVA
Capacity and current freed
10.5 kVA (10.5%)
Annual energy at this load
340,000 kWh
Excess reactive energy a year
98,960 kVArh
Reactive charges a year now
£297
After correction
£0
Saving a year
£297
WorkingPF = kW ÷ kVA = 85 ÷ 100 = 0.85kVAr = 85 × (tan(acos 0.85) − tan(acos 0.95)) = 85 × (0.620 − 0.329) = 24.7 kVAr

Reactive charges apply to half-hourly metered sites. The estimate assumes a steady load and power factor; real sites vary, so size a bank from logged data and a survey.

Ask PES to check your reactive charges

What power factor is

An AC supply carries two kinds of power. Real power, in kW, does useful work: heat, light and turning shafts. Reactive power, in kVAr, is the magnetising current that motors, transformers and fluorescent ballasts need to operate. It does no work but still flows through your cables and the network. Apparent power, in kVA, is the total the supply has to carry.

kVA² = kW² + kVAr²
Power factor = kW ÷ kVA = cos(phase angle)

A site with lots of motors, pumps and compressors typically sits at 0.75 to 0.9 lagging, which means the network carries 11 to 33% more current than the work needs.

How to use the power factor calculator

With half-hourly bill or meter data, use the kW and kVA mode with readings from the same period. With a clamp meter reading, use the volts and amps mode, which works out the kVA first:

Single-phase: kVA = volts × amps ÷ 1,000
Three-phase: kVA = 1.732 × volts × amps ÷ 1,000

For the kVA side of the triangle on its own, the kW to kVA calculator and the kVA to amps calculator handle the conversions.

Power factor correction: how much kVAr you need

Capacitors supply reactive power locally, so less of it has to come through the network. The correction needed to move from one power factor to another is:

kVAr needed = kW × (tan(acos PF now) − tan(acos PF target))

Worked example: an 85 kW site at 0.85

A site drawing 85 kW and 100 kVA has a power factor of 0.85, a phase angle of 31.8° and 52.7 kVAr of reactive power. To reach 0.95 it needs 85 × (0.620 − 0.329) = 24.7 kVAr, so in practice a 25 kVAr bank. After correction it draws 85 ÷ 0.95 = 89.5 kVA, freeing 10.5 kVA of capacity and cutting the current by 10.5%.

Worked example: a three-phase workshop

A workshop on a 400 V supply draws 250 A per phase while using 140 kW. Its apparent power is 1.732 × 400 × 250 ÷ 1,000 = 173.2 kVA, so its power factor is 140 ÷ 173.2 = 0.808. Reaching 0.95 takes 56.0 kVAr, so a 60 kVAr bank. That brings the demand down to 147.4 kVA, freeing 25.8 kVA. At 4,000 hours a year and 0.3p/kVArh, its reactive charges are about £672 a year before correction.

Correction table: kVAr per kW of load

Multiply your load in kW by the figure in the table. For example, 100 kW at 0.80 needs 42.1 kVAr to reach 0.95.

Power factor nowTo 0.95To 0.98To 1.00
0.700.6920.8171.020
0.750.5530.6790.882
0.800.4210.5470.750
0.850.2910.4170.620
0.900.1560.2810.484
0.920.0970.2230.426

Why network operators charge for reactive power

Reactive current heats cables and transformers and uses up network capacity just as real current does, so the distribution network operator (DNO) charges for it. On a half-hourly supply, the excess reactive power charge applies to the kVArh in each half hour above 33% of the kWh, which is the same as a power factor of about 0.95. Your supplier passes it through as a bill line in p/kVArh. A site at 0.95 or better pays nothing on it.

Power factor also hits the capacity charge. Your agreed supply capacity is set in kVA, so a site at 0.85 needs about 12% more kVA than the same load at 0.95, and pays for it every day. If you are near your limit, correction can avoid an excess capacity charge or a costly upgrade.

Capacitor banks

Most sites correct power factor with a capacitor bank at the main switchboard; the calculator’s payback section shows whether one is worth it. A fixed bank suits a steady load. An automatic bank switches capacitor steps in and out as the load changes, so it holds the target without over-correcting into a leading power factor when the site is quiet. Sites with variable speed drives or other harmonic sources need a detuned bank, which has reactors to stop the capacitors resonating with the harmonics. Size one from a survey with a few weeks of logged data.

Why power factor matters for a business: payback

The saving from correction has up to three parts: the reactive charges that disappear, any capacity charge saved by lowering your agreed capacity and a small cut in cable and transformer losses. For the 85 kW example, the reactive charges are about £297 a year at 0.3p/kVArh. If the freed 10.5 kVA lets you lower your agreed capacity at 5p/kVA a day, that adds about £192 a year. On a quote of £1,500, the simple payback would be about 5.1 years on reactive charges alone, or 3.1 years with the capacity saving.

Correction pays back fastest on large, steady motor loads with a poor power factor. Before you buy, check what you actually pay on your bill. You can check the three-phase load itself with the three-phase power calculator. If you want a second opinion on your reactive and capacity charges, or your supply contract, talk to PES.

Frequently asked questions

How do you calculate power factor?

Divide real power in kW by apparent power in kVA. A site drawing 85 kW and 100 kVA has a power factor of 85 ÷ 100 = 0.85.

What is a good power factor?

0.95 or above. Below 0.95, network operators charge half-hourly sites for the excess reactive power, so most sites aim for 0.95 to 0.98 after correction.

How much kVAr do I need to correct power factor?

Multiply the kW by tan(acos(current PF)) minus tan(acos(target PF)). Taking an 85 kW load from 0.85 to 0.95 needs 85 × (0.620 − 0.329) = 24.7 kVAr, so a 25 kVAr capacitor bank.

What is a reactive power charge?

It is a network charge for reactive energy, measured in kVArh, above an allowance of about a third of your kWh, which is the same as a power factor of 0.95. At 0.3p/kVArh, an 85 kW site at a power factor of 0.85 running 4,000 hours a year pays about £297 a year.

What is the difference between kW, kVA and kVAr?

kW is real power that does useful work, kVAr is reactive power that motors and transformers need to run and kVA is the total the supply has to carry. They form a right-angled triangle, so kVA² = kW² + kVAr²; 85 kW and 52.7 kVAr make 100 kVA.

Is power factor correction worth it?

It depends on your charges. Correcting an 85 kW site from 0.85 to 0.95 saves about £297 a year in reactive charges at 0.3p/kVArh and frees 10.5 kVA of capacity. If that lets you lower your agreed capacity at 5p/kVA a day, it saves about £192 a year more.

Does power factor affect my electricity bill?

Yes, if you are half-hourly metered. Reactive charges appear as a separate line, and your capacity charge is set in kVA, so a site at 0.85 needs about 12% more capacity than the same load at 0.95. Smaller non half-hourly sites are not charged for reactive power.

Can you over-correct power factor?

Yes. Too much capacitance makes the power factor leading, which can raise the voltage and interact with harmonics. Automatic capacitor banks avoid this by switching steps in and out to match the load.