Three Phase Power Calculator

This three phase power calculator works out the real power in kW, the apparent power in kVA and the reactive power in kVAr from the line to line voltage, the current per phase and the power factor. It uses the UK 400 V standard by default and suits anything from a single machine to a whole site supply.

Free calculator

Three-phase power from volts and amps

V
A

UK three-phase supplies are 400 V line to line, 230 V line to neutral. Use a power factor of 1 for heaters and EV chargers, 0.8 to 0.9 for motors, and 0.9 for a mixed business site. Assumes a balanced load, with the same current on each phase.

Real power
62.4kW

100 A per phase at 400 V, power factor 0.9

Apparent power69.3 kVA
Reactive power30.2 kVAr
Real power per phase20.8 kW
Phase voltage (line to neutral)230.9 V
MeteringWhole current (up to 100 A)
WorkingkW = 1.732 × 400 V × 100 A × 0.9 ÷ 1,000 = 62.4 kW. kVA = 1.732 × 400 V × 100 A ÷ 1,000 = 69.3 kVA. Phase voltage = 400 V ÷ 1.732 = 230.9 V

This gives the power for a balanced load. Cable and protective device sizing must be done by a qualified electrician to BS 7671.

Talk to PES about your supply

How the three phase power calculator works

A three-phase supply has three live conductors, each carrying an alternating current 120 degrees out of step with the others. For a balanced load, where each phase carries the same current, total power is:

kW = 1.732 × line to line volts × amps per phase × power factor ÷ 1,000
kVA = 1.732 × line to line volts × amps per phase ÷ 1,000
kVAr = √(kVA² − kW²)

The 1.732 is the square root of 3. It appears because the voltage between two lines is √3 times the voltage between one line and neutral, a result of the 120 degree spacing between phases.

Line voltage and phase voltage

UK three-phase supplies are 400/230 V. The 400 V is measured between any two lines (line to line). The 230 V is measured between any line and neutral (phase voltage), which is what a single-phase socket gets. 400 ÷ 1.732 = 230.9 V, so the two figures are the same system described two ways. If you only know the phase voltage, the equivalent formula is kW = 3 × phase volts × amps × power factor ÷ 1,000.

Worked example: a 100 A supply

A small office or shop on a 100 A three-phase supply has an apparent power capacity of 1.732 × 400 × 100 ÷ 1,000 = 69.3 kVA. At a power factor of 0.9 that is 62.4 kW of real power, with 30.2 kVAr of reactive power. 100 A per phase is also the limit for whole-current metering, which is why 69 kVA is the point where sites move to CT metering.

Worked example: a 63 A machine

A CNC machine on a 63 A three-phase supply, with a motor-driven power factor of 0.85, draws 1.732 × 400 × 63 × 0.85 ÷ 1,000 = 37.1 kW at full load. Its apparent power is 43.6 kVA and its reactive power 23.0 kVAr. It is the 43.6 kVA, not the 37.1 kW, that counts against the site’s supply capacity.

Unbalanced loads

Real sites are rarely perfectly balanced. If each phase carries a different current, work out each phase separately with the phase voltage and add them. With 80 A, 95 A and 70 A on the three phases at 230 V and a power factor of 0.9, the total is 230 × (80 + 95 + 70) × 0.9 ÷ 1,000 = 50.7 kW.

Three-phase current to kW table

Real power at 400 V line to line for common current ratings. The PF 1 column also equals the kVA at any power factor.

Current per phasePF 0.85PF 0.9PF 1
16 A9.4 kW10.0 kW11.1 kW
20 A11.8 kW12.5 kW13.9 kW
32 A18.8 kW20.0 kW22.2 kW
40 A23.6 kW24.9 kW27.7 kW
63 A37.1 kW39.3 kW43.6 kW
80 A47.1 kW49.9 kW55.4 kW
100 A58.9 kW62.4 kW69.3 kW
125 A73.6 kW77.9 kW86.6 kW
160 A94.2 kW99.8 kW110.9 kW
200 A117.8 kW124.7 kW138.6 kW
250 A147.2 kW155.9 kW173.2 kW
315 A185.5 kW196.4 kW218.2 kW
400 A235.6 kW249.4 kW277.1 kW
500 A294.4 kW311.8 kW346.4 kW
630 A371.0 kW392.8 kW436.5 kW
800 A471.1 kW498.8 kW554.3 kW
1,000 A588.9 kW623.5 kW692.8 kW

To go from a known load to the current it draws, use the kW to amps calculator. To start from a kVA rating instead, try the kVA to amps calculator.

How three-phase power relates to capacity and metering

Nearly every UK business with more than a small office load runs on three-phase. The current per phase decides how the supply is metered. Up to 100 A per phase, about 69 kVA, a whole-current meter carries the load directly. Above that, current transformers (CTs) step the current down for the meter, and the site is usually half-hourly settled, with each 30-minute period of use recorded and priced.

The kVA figure is what the network cares about. Your agreed supply capacity is set in kVA, and you pay a daily charge for every kVA of it. Measuring the current on each phase at the busiest time of day, and running it through this calculator, tells you how close you are to that capacity before you add machinery, heat pumps or EV chargers. A low power factor raises the kVA for the same kW, which is why improving it can free up capacity; the power factor calculator shows by how much.

If the numbers show you are near your limit, or paying for far more capacity than you use, PES can review your supply and tender your contract across the market.

Frequently asked questions

How do you calculate three-phase power?

Multiply 1.732 by the line to line voltage, the current per phase and the power factor, then divide by 1,000 for kW. A 50 A load at 400 V and a power factor of 0.9 is 1.732 × 400 × 50 × 0.9 ÷ 1,000 = 31.2 kW.

How many kW is a 100 A three-phase supply?

A 100 A three-phase supply at 400 V is 69.3 kVA. That is 62.4 kW at a power factor of 0.9 and 69.3 kW at a power factor of 1. It is also the largest supply that can use a whole-current meter.

How many kW is 63 A three-phase?

63 A at 400 V three-phase is 43.6 kVA. That gives 39.3 kW at a power factor of 0.9, or 37.1 kW at 0.85, which is typical for a motor load.

How many kW is 32 A three-phase?

32 A at 400 V three-phase is 22.2 kVA, or 22.2 kW at a power factor of 1. That is why 22 kW EV chargers run on a 32 A three-phase supply. At a power factor of 0.9 it is 20.0 kW.

Why is three-phase 400 V and single-phase 230 V?

They are the same supply measured two ways. 400 V is between two lines and 230 V is between one line and neutral. The line voltage is 1.732 times the phase voltage, and 400 ÷ 1.732 = 230.9 V.

Why is there a √3 in the three-phase power formula?

The three phases are 120 degrees apart, so the voltage between two lines is √3, about 1.732, times the voltage from line to neutral. Using the 400 V line voltage with 1.732 gives the same total as 3 × 230.9 V for a balanced load.

How do you calculate power on an unbalanced three-phase load?

Work out each phase separately using the 230 V phase voltage and add the results. With 80 A, 95 A and 70 A at a power factor of 0.9, the total is 230 × 245 × 0.9 ÷ 1,000 = 50.7 kW.

Can I use this to size a cable or breaker?

No. It gives the power for a known current. Cable size and protection depend on installation method, length, grouping and temperature, and must be designed by a qualified electrician to BS 7671.