Skip to main content

Heat Pump Running Cost Calculator: Heat Pump vs Gas Boiler

This heat pump running cost calculator compares what your building pays to heat with a gas boiler against what an air source heat pump would cost to run, using your gas use, boiler efficiency, heat pump SCOP and unit rates. It also gives the break-even SCOP: the efficiency the heat pump needs just to match the boiler.

Free calculator

Heat pump vs gas boiler running cost

kWh

Use the gas that goes on space heating and hot water from your bills. Leave out catering or process gas that the heat pump would not replace. Bills in therms or meter units? Convert them first.

%

A modern condensing boiler runs at about 85 to 90% in practice, an older one nearer 75 to 80%. Air source heat pumps usually achieve a SCOP of 2.5 to 4: higher with low flow temperatures and a well insulated building, lower with old radiators run hot.

p/kWh
p/kWh

26p/kWh and 10p/kWh are typical business rates. Use the unit rates from your own contracts.

Add standing charges (optional)
p/day
p/day

Only add the gas standing charge if the heat pump would let you remove the gas supply completely. Add an electricity figure only if your standing or capacity charges would rise, for example after a supply upgrade.

Running cost a year

Gas boiler now

£15,000

Heat pump

£11,050

At a SCOP of 3 and your unit rates

The heat pump costs £3,950 a year less to run, 26.3% below gas.
Saving a year£3,950
Heat delivered127,500 kWh
Electricity the heat pump needs42,500 kWh
Cost per kWh of heat, gas boiler11.8p
Cost per kWh of heat, heat pump8.7p
Break-even SCOP, unit rates only2.21
WorkingHeat = 150,000 kWh × 85% = 127,500 kWh. Electricity = 127,500 ÷ 3 = 42,500 kWh. Break-even SCOP = 26 × 85% ÷ 10 = 2.21.

Running costs only. Installation, maintenance and any supply upgrade are not included, and real SCOP depends on the system design and flow temperature.

Talk to PES about your energy costs

How the heat pump running cost calculator works

A boiler turns gas into heat at its efficiency, so the first step is the heat your building actually needs. The heat pump delivers that heat using electricity divided by its SCOP.

Heat demand = gas kWh × boiler efficiency
Heat pump electricity = heat demand ÷ SCOP
Running cost = kWh × unit rate

Standing charges are left out by default. If switching would let you remove the gas supply entirely, add the gas standing charge in the optional section.

COP vs SCOP

COP (coefficient of performance) is heat out divided by electricity in at one test point, such as 7°C outside and 35°C water, and brochures often quote 4 or more. SCOP (seasonal COP) averages a whole heating season, including cold spells, defrost cycles and hot water. It is lower, and it is the figure that sets your annual bill.

The spark gap explained

The spark gap is the difference between electricity and gas prices. At 26p/kWh and 10p/kWh, a kWh of electricity costs 2.6 times as much as a kWh of gas, and a heat pump has to make up that gap through efficiency before it saves anything.

Break-even SCOP = electricity rate × boiler efficiency ÷ gas rate

With an 85% boiler that is 26 × 0.85 ÷ 10 = 2.21: every kWh of electricity must become at least 2.21 kWh of heat to match the boiler. A well designed system clears that. One running at high flow temperatures may only manage 2.5 or less, leaving little or no saving. At UK business prices the spark gap is the main reason heat pumps do not always beat gas on running cost.

Running cost by SCOP

The default building uses 150,000 kWh of gas a year in an 85% boiler, which is 127,500 kWh of heat, with electricity at 26p/kWh and gas at 10p/kWh. The boiler costs £15,000 a year, or 11.8p per kWh of heat.

SCOPElectricityHeat pump costCost per kWh of heatVs gas
2.063,750 kWh£16,57513.0p£1,575 more
2.257,955 kWh£15,06811.8p£68 more
2.551,000 kWh£13,26010.4p£1,740 less
2.845,536 kWh£11,8399.3p£3,161 less
3.042,500 kWh£11,0508.7p£3,950 less
3.536,429 kWh£9,4717.4p£5,529 less
4.031,875 kWh£8,2886.5p£6,713 less

How flow temperature affects SCOP

The lower the water temperature a heat pump has to produce, the higher its SCOP. A system designed for 35 to 45°C, with larger radiators or underfloor heating, usually reaches 3 to 4. Dropping a heat pump onto old radiators run at 55°C or more often pulls it to 2.5 or below, which is why a heat loss survey and emitter design matter as much as the unit itself.

Worked examples

A 150,000 kWh office at a SCOP of 3

The boiler uses 150,000 kWh of gas at 10p, costing £15,000. The building needs 127,500 kWh of heat, so the heat pump uses 42,500 kWh of electricity, costing £11,050 at 26p. It saves £3,950 a year, 26.3% less than gas.

The same office at a SCOP of 2.2

Run hot and averaging 2.2, the heat pump needs 57,955 kWh and costs £15,068, £68 a year more than gas, because it sits just below the break-even of 2.21.

A small office with an older boiler

A building using 60,000 kWh of gas in an 80% boiler needs 48,000 kWh of heat and pays £6,000. A heat pump at a SCOP of 3.5 uses 13,714 kWh, costing £3,566, a saving of £2,434 or 40.6%. The older boiler lowers the break-even to 2.08.

Ways to improve the economics

Electricity tariffs. The break-even SCOP falls with your electricity rate. A time of use tariff that runs the heat pump on cheaper overnight power, or a better tendered contract, moves the result more than almost anything else.

Electricity rateRatio to 10p gasBreak-even SCOPSaving at SCOP 3
18p/kWh1.81.53£7,350
20p/kWh2.01.70£6,500
22p/kWh2.21.87£5,650
26p/kWh2.62.21£3,950
30p/kWh3.02.55£2,250

Solar. On site solar is cheaper than grid power, though most of it arrives in summer when heating demand is low. Our solar panel calculator shows what a roof could generate.

Building fabric. Insulation, draught proofing and better controls cut the heat demand, which shrinks the heat pump and lets it run cooler at a higher SCOP.

Why it matters for a business

Moving heating from gas to electricity changes both contracts: electricity use and peak demand rise, which can affect your supply capacity and price, while a smaller gas load may be priced less well. If your bills are in therms, convert them with our therms to kWh converter, and model the total bill with the energy cost calculator. We can then tender both contracts for the new profile.

This compares running costs only. It excludes installation, grants, maintenance and any supply upgrade, and real SCOP depends on the design, so get a heat loss survey first.

Frequently asked questions

How much does it cost to run a heat pump for a business?

It depends on the heat demand, the SCOP and your electricity rate. A building using 150,000 kWh of gas a year in an 85% boiler needs 127,500 kWh of heat, and a heat pump with a SCOP of 3 at 26p/kWh costs about £11,050 a year to deliver it.

Is a heat pump cheaper to run than a gas boiler?

Only if its SCOP beats the break-even. At 26p/kWh electricity, 10p/kWh gas and an 85% boiler the break-even SCOP is 2.21, so a heat pump at a SCOP of 3 costs 26.3% less to run, while one averaging 2.2 costs slightly more than gas.

What is a good SCOP for an air source heat pump?

A well designed system running at a 35 to 45°C flow temperature usually reaches a SCOP of 3 to 4. A SCOP of 2.5 or below points to high flow temperatures or a poor design, and at typical UK business rates leaves little or no saving over gas.

What is the spark gap?

The spark gap is the difference between the price of electricity and the price of gas. At 26p/kWh and 10p/kWh electricity costs 2.6 times as much per kWh, and a heat pump has to overcome that through efficiency before it saves money.

How do you work out the break-even SCOP?

Multiply the electricity rate by the boiler efficiency and divide by the gas rate. At 26p/kWh, 85% and 10p/kWh that is 26 × 0.85 ÷ 10 = 2.21. At 20p/kWh electricity it falls to 1.70.

What is the difference between COP and SCOP?

COP is the heat out divided by the electricity in at a single test point, often 4 or more at 7°C outside and a 35°C flow. SCOP averages performance over a whole heating season, including cold weather and defrost cycles, so it is lower and is the right figure for annual running costs.

How much electricity does a heat pump use?

Divide the heat demand by the SCOP. Replacing 150,000 kWh of gas in an 85% boiler with a heat pump at a SCOP of 3 needs 42,500 kWh of electricity a year, or 36,429 kWh at a SCOP of 3.5.

Will I still pay a gas standing charge after fitting a heat pump?

Yes, unless the gas supply is removed entirely. If you keep gas for catering, hot water or a backup boiler the standing charge stays, so only add it to the comparison if you would disconnect.

Weighing up a heat pump? We can model the change to your gas and electricity costs and tender both contracts for the new load.

Get in touch